PERFORMANCE OF A LOW-ENERGY HOUSE IN A MILD COOLING SEASON .1. THERMAL PERFORMANCE OF THE HOUSE

被引:1
作者
MA, B [1 ]
UGURSAL, VI [1 ]
机构
[1] TECH UNIV NOVA SCOTIA,DEPT MECH ENGN,POB 1000,HALIFAX B3J 2X4,NS,CANADA
关键词
LOW ENERGY HOUSE; COOLING PERFORMANCE; HEAT PUMP;
D O I
10.1002/er.4440170709
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A low-energy house located in Halifax, Canada, was monitored for a year using a computerized data acquisition system. Data on indoor and outdoor temperatures, relative humidities, and power consumption were collected for a whole year. The results of the analysis of cooling season data are presented. It was found that indoor temperature variations in the house were generally small, indicating a high level of comfort. The cooling load, and the cooling energy requirement of the house were low owing to the high level of insulation, and could further be reduced by increasing the thermostat setting. This however would reduce the comfort level in the house. Temperature set-up during unoccupied periods did not reduce daily cooling energy requirement, and addition of an economizer control would not be feasible owing to the small magnitude of potential savings.