AN INVESTIGATION OF BREAKDOWN VOLTAGE WITH SMALL ARC CURRENT DUE TO POOR CONTACT IN SF6 GAS

被引:3
|
作者
SUGIYAMA, S
MORITA, T
HOSOKAWA, T
SEKIYA, Y
MUKAIYAMA, Y
TAKAGI, I
LEE, KS
机构
[1] CHUBU ELECT POWER CO INC, NAGOYA, JAPAN
[2] NAGOYA INST TECHNOL, NAGOYA, AICHI 466, JAPAN
[3] YOUNGNAM UNIV, KYONG SAN, SOUTH KOREA
[4] DAIDO INST TECHNOL, NAGOYA, JAPAN
关键词
GAS INSULATED SWITCHGEAR; HOT GAS; BREAKDOWN VOLTAGE;
D O I
10.1109/61.108926
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Using an experimental apparatus modeled for the contact portion of a gas insulated switchgear(GIS), the influence of the distance between the portion and the dead tank of the GIS and arc duration on the breakdown voltage was investigated. This was conducted both experimentally and theoretically for the case when the arc was ignited in the portion. In the theoretical analysis, profiles of flow velocity and gas density were calculated (known as fluid analysis). Breakdown voltage evaluated through the gas density was in relatively good agreement with that of the experiment.
引用
收藏
页码:332 / 338
页数:7
相关论文
共 50 条
  • [1] BREAKDOWN MECHANISM OF A GAP WITH A SMALL ARC CURRENT IN SF6 GAS
    SUGIYAMA, S
    MORITA, T
    HOSOKAWA, T
    SEKIYA, Y
    LEE, KS
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1994, 1 (06) : 1167 - 1174
  • [3] Breakdown probability of SF6 due to voltage transients
    Meijer, S
    Morshuis, PHF
    Smit, JJ
    2004 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2004, : 502 - 505
  • [4] HEAVY CURRENT CLOGGING PHENOMENA IN SF6 GAS ARC
    MURANO, M
    NISHIKAW.H
    KOBAYASH.A
    IWAMOTO, T
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1974, PA93 (06): : 1735 - 1735
  • [5] Investigation of Arc Splitters in an SF6 Insulated Medium Voltage Switchgear
    Novak, B.
    Sonar, R.
    Sivaraj, R.
    2017 63RD IEEE HOLM CONFERENCE ON ELECTRICAL CONTACTS, 2017, : 242 - 248
  • [6] Investigation of Discharge Propagation in Localized High-Temperature SF6 Gas With Breakdown Voltage Measurement
    Kotsuji, Hideyuki
    Kuroda, Mami
    Terada, Masanao
    Shiraishi, Katsuhiko
    Urai, Hajime
    Yokomizu, Yasunobu
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2023, 51 (02) : 429 - 436
  • [7] Arc erosion characteristics of Cu-W contact at load current range in SF6 gas
    Hori, Koichi
    Ohtsuka, Masao
    Hara, Masanori
    Electrical Engineering in Japan (English translation of Denki Gakkai Ronbunshi), 1997, 118 (01): : 41 - 51
  • [8] BREAKDOWN AND ARC-OVER OF SF6 INSULATIONS
    MOSCH, W
    PERIODICA POLYTECHNICA-ELECTRICAL ENGINEERING, 1975, 19 (03): : 267 - 284
  • [9] PD inception and breakdown voltage characteristics in PFC and SF6 gas mixtures
    Ohtsuka, S
    Koumura, M
    Eguchi, K
    Cho, MG
    Yuasa, S
    Okabe, S
    Hikita, M
    GASEOUS DIELECTRICS IX, 2001, : 211 - 216
  • [10] Breakdown temperature of electrons in SF6 gas
    Uhm, Han S.
    Choi, Eun H.
    Cho, Guangsup
    Ryu, Han-Yong
    APPLIED PHYSICS LETTERS, 2010, 97 (16)