AN INVESTIGATION OF BREAKDOWN VOLTAGE WITH SMALL ARC CURRENT DUE TO POOR CONTACT IN SF6 GAS

被引:3
作者
SUGIYAMA, S
MORITA, T
HOSOKAWA, T
SEKIYA, Y
MUKAIYAMA, Y
TAKAGI, I
LEE, KS
机构
[1] CHUBU ELECT POWER CO INC, NAGOYA, JAPAN
[2] NAGOYA INST TECHNOL, NAGOYA, AICHI 466, JAPAN
[3] YOUNGNAM UNIV, KYONG SAN, SOUTH KOREA
[4] DAIDO INST TECHNOL, NAGOYA, JAPAN
关键词
GAS INSULATED SWITCHGEAR; HOT GAS; BREAKDOWN VOLTAGE;
D O I
10.1109/61.108926
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Using an experimental apparatus modeled for the contact portion of a gas insulated switchgear(GIS), the influence of the distance between the portion and the dead tank of the GIS and arc duration on the breakdown voltage was investigated. This was conducted both experimentally and theoretically for the case when the arc was ignited in the portion. In the theoretical analysis, profiles of flow velocity and gas density were calculated (known as fluid analysis). Breakdown voltage evaluated through the gas density was in relatively good agreement with that of the experiment.
引用
收藏
页码:332 / 338
页数:7
相关论文
共 9 条
[1]  
Amsden A. A., 1980, SALE SIMPLIFIED ALE
[2]   A THERMALLY TRIGGERED SPARK GAP [J].
BROADBENT, TE ;
WOOD, JK .
BRITISH JOURNAL OF APPLIED PHYSICS, 1955, 6 (10) :368-370
[3]   EFFECT OF PLASMA-JET IN DOUBLE ELECTRODE SPARK GAP [J].
ISHIKAWA, T .
JOURNAL OF THE PHYSICAL SOCIETY OF JAPAN, 1964, 19 (03) :367-&
[4]   BREAKDOWN IN TRIGGERED SPARK GAPS IN AIR [J].
KUFFEL, E ;
BERA, MM .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1968, PA87 (07) :1628-+
[5]  
KURIMOTO A, 1973, T IEE JAPAN A, V93, P199
[6]  
NAGATA M, 1984, T IEE JAPAN, V104
[7]  
Sletten A., 1957, P I ELECTR ENG, V104, P54, DOI [10.1049/pi-c.1957.0008, DOI 10.1049/PI-C.1957.0008]
[8]  
YANABU S, 1989, IEEE T PWRD, V4
[9]  
YOSHIZUMI T, 1989, IEEE T PWRD, V4